0.6/1 kV 3×185+1×95 LV POWER CABLES
Basic Info
Model No.: YJY
Product Description
1. APPLICALBE STANDARDS
The cable shall be designed, manufactured and tested according to international standards as follows:
Quality Control Standard | |
ISO 9001 | Quality Management Systems |
ISO 14001 | Environmental Management Systems |
Component Material Standard | |
IEC 60228 | Conductors of insulated cables |
Cable Standard | |
IEC 60502-1 | Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3kV(Um=3.6kV) |
IEC 60332-3-24 | Test for vertical flame spread of vertically-mounted bunched wires or cables – Category C |
2. CABLES STRUCTURE FOR 0.6/1KV CABLE
1)
CU/PVC/PVC/STA/FR-PVC 0.6/1 kV 3×185+1×95
Basic Structure | Nominal Thickness mm | Nominal Outer Diameter mm |
1.Copper conductor | / | 15.3 |
2.XLPE insulation | 1.6 | 18.5 |
3. Filler | / | 42.4 |
4. Wrapping tape | 0.2 | 43.0 |
5. PVC Inner sheath | 1.4 | 45.8 |
6. Galvanized steel tape armor | 0.5 | 47.8 |
7. FR-PVC Outer sheath | 2.6 | 53.0 |
3. TEST REQUIREMENTS FOR LV POWER CABLES
The cable testing shall be conducted in accordance with applicable standard of 0.6/1kV Power Cables. The following test items shall be carried out in accordance with relevant IEC standards.
No. | Test item |
Routine tests | |
1 | measurement of the electrical resistance of conductors |
2 | Voltage test |
Sample tests | |
1 | conductor examination |
2 | check of dimensions |
3 | Hot set test for XLPE insulation |
4. PACKING PARTICULARS FOR 0.6/1KV POWER CABLES
The cables shall be wound on steel-wooden drums. The indelible marking shall be printed on the surface of drum flange in accordance with customer requirements.